PLEASE NOTE:
Floor Sensor Probes must be installed into a separate conduit that will always be accessible if removal of sensor is ever required. The sensor conduit with no more than one bend shall be installed from the floor to the thermostat or junction box located directly above the heated area.
Floor Sensor
Thermostat comes with "New Mounting Plate".
Floor Sensor included with Thermostat.
Sensor Cable can be extended up to 50m (using 2 x 1.5mm2)
Connection Diagrams:
IMPORTANT:
To prevent damage to the thermostat a suitably sized contactor MUST be used for loads over 16 Amps. Contactor sizing and installation must be in accordance with the manufacturer's recommendations.