DEVI offers a large variety of underfloor heating systems
 
 
 
 
 
 
 
 
 
 
 
 
   
General Information Technical Information

Devireg™ 330

Technical Reference

Voltage
240V ~
Maximum Load
10/16 Amps
Inductive Load
3 Amp
Change-over Switch
NO/NC
Hysteresis (degree of accuracy)
0.2°C
Control Light
LED diode
Mounting
DIN Rail
Standard Sensor Length
2.5m
Economy Set Back
5°C
Product Code
Temperature Range 
Economy Set-Back
Sensor
Moisture Proof
19113620
-10°C to +10°C
-
Floor Probe
IP 65
19113638
+5°C to +45°C
5°C
Floor Probe
IP65
19113648
+15°C to +30°C
5°C
Air Sensor
IP 20
19113653
+30°C to +90°C
-
Floor Probe
IP 65
19113661
+60°C to +160°C
-
Floor Probe
IP 65
PLEASE NOTE:
Floor Sensor Probes must be installed into a separate conduit that will always be accessible if removal of sensor is ever required. The sensor conduit with no more than one bend shall be installed from the floor to the thermostat or junction box located directly above the heated area.

Floor Sensor included with Thermostat. 
Sensor Cable can be extended up to 50m (using 2 x 1.5mm2)

Connection Diagrams:

Devireg 330 Heating Connection Diagram

Devireg 330 Cooling Connection Diagram

Heating

Cooling

IMPORTANT: 

To prevent damage to the thermostat a suitably sized contactor MUST be used for loads over 16 Amps. Contactor sizing and installation must be in accordance with the manufacturer's recommendations.

PDF Installation & Use Guide